Description
Key Features:
Dual-Wall Construction (RCS-RA3):
The RCS-RA3 features a dual-wall design with an inner hot melt adhesive lining that enhances sealing against moisture, contaminants, and other environmental factors, ensuring optimal performance.
UV Resistant:
Designed to withstand prolonged outdoor exposure, the tubing offers excellent UV resistance, maintaining integrity even in harsh weather conditions.
Flame Retardant:
Meets industry standards for controlled flammability, making it suitable for medium and high-voltage applications where safety is critical.
Semi-Rigid Design:
Combines flexibility with superior mechanical strength, making the tubing ideal for versatile installation in challenging environments.
Shrink Ratio 3:1:
With a 3:1 shrink ratio, the tubing accommodates a wide range of cable sizes, reducing inventory requirements and simplifying installation processes.
Custom Lengths:
Available in custom lengths up to 1.5 meters, providing flexibility for various installations and reducing waste.
High-Temperature Performance:
The tubing fully recovers at a minimum temperature of 120℃, ensuring a tight and secure fit for reliable insulation and protection.
Applications:
Cable Insulation and Protection:
Ideal for medium and high-voltage cables, providing robust mechanical protection and sealing in environments where durability and safety are paramount.
Harsh Environmental Conditions:
Perfect for installations requiring UV resistance, moisture sealing, and mechanical durability, such as outdoor or underground applications.
Why Choose RCS-RA3/RCS-R3 Heat Shrink Tubing?
The RCS-RA3/RCS-R3 Heat Shrink Tubing delivers superior protection for medium and high-voltage cables. Whether you choose the version with hot melt adhesive lining for enhanced sealing or the standard design, this semi-rigid tubing provides reliable moisture protection, UV resistance, and mechanical strength, making it ideal for demanding industrial applications.
Shelf Life & Storage:
The RCS-RA3/RCS-R3 Heat Shrink Tubing has an extended shelf life of 5+ years when stored in a humidity-controlled environment (temperature range -10°C to 40°C, relative humidity <75%).
Ordering Information:
- Standard Colors: Black (other colors available upon request)
Typical technical performances:
Test Items |
Test Method |
Test Requirements |
Tensile strength | ASTM D 2671 | 12MPa min. |
Ultimate elongation | ASTM D 2671 | 350% min. |
Tensile strength after
Aging at 150℃ for 168hrs |
ASTM D 2671 | 12MPa min. |
Ultimate elongation after
Aging at 150℃for 168hrs |
ASTM D 2671 | 300% min. |
Density | ASTM D 792 | 1.0~1.1g/cm3 |
Dielectric strength | ASTM D 60243 | 12kV/mm(2mm) min. |
Volume resistivity | ASTM D 2671 | 1012Ω.cm min. |
Low-temperature flexibility
-40℃/4hrs |
ASTM D 2671 | No cracking of the outer jacket |
Properties of hot melt adhesive | ||
Softening point | ASTM E28 | 85+/-5℃ |
Peel strength(PE) | ASTM D 2671 | 4N/cm min. |
Water absorption | ISO 62 | 0.2% max. |
Dimensions:
RCS-RA3 Heavy wall tubing with hot melting adhesive |
|||||||||
Size
(mm) |
As supplied
(mm) |
After recovered
(mm) |
Standard length
(m) |
Size
(mm) |
As supplied
(mm) |
After recovered
(mm) |
Standard length
(m) |
||
D*(Min.) | d*(Max.) | w*(Min.) | D*(Min.) | d*(Max.) | w*(Min.) | ||||
9/3 | 9 | 3 | 2.0 | 1.0-1.5 | 105/25 | 105 | 25 | 4.5 | 1.0-1.5 |
15/4 | 15 | 4 | 2.4 | 1.0-1.5 | 115/34 | 115 | 34 | 4.2 | 1.0-1.5 |
22/6 | 22 | 6 | 2.7 | 1.0-1.5 | 130/36 | 130 | 36 | 4.2 | 1.0-1.5 |
33/8 | 33 | 8 | 3.2 | 1.0-1.5 | 180/50 | 180 | 50 | 4.2 | 1.0-1.5 |
45/12 | 45 | 12 | 4.0 | 1.0-1.5 | 200/60 | 200 | 60 | 4.2 | 1.0-1.5 |
55/16 | 55 | 16 | 4.0 | 1.0-1.5 | 235/65 | 235 | 65 | 4.4 | 1.0-1.5 |
65/19 | 65 | 19 | 4.0 | 1.0-1.5 | 265/75 | 265 | 75 | 4.8 | 1.0-1.5 |
75/22 | 75 | 22 | 4.0 | 1.0-1.5 | 300/85 | 300 | 85 | 4.8 | 1.0-1.2 |
85/25 | 85 | 25 | 4.2 | 1.0-1.5 | 350/100 | 350 | 100 | 4.8 | 1.0-1.2 |
95/29 | 95 | 29 | 4.2 | 1.0-1.5 | 385/110 | 385 | 110 | 4.8 | 1.0-1.2 |
RCS-R3 Heavy wall tubing without hot melting adhesive |
|||||||||
Size
(mm) |
As supplied
(mm) |
After recovered
(mm) |
Standard length
(m) |
Size
(mm) |
As supplied
(mm) |
After recovered
(mm) |
Standard length
(m) |
||
D*(Min.) | d*(Max.) | w*(Min.) | D*(Min.) | d*(Max.) | w*(Min.) | ||||
9/3 | 9 | 3 | 2.0 | 1.0-1.5 | 95/29 | 95 | 29 | 4.2 | 1.0-1.5 |
15/4 | 15 | 4 | 2.4 | 1.0-1.5 | 115/34 | 115 | 34 | 4.2 | 1.0-1.5 |
22/6 | 22 | 6 | 2.7 | 1.0-1.5 | 130/36 | 130 | 36 | 4.2 | 1.0-1.5 |
33/8 | 33 | 8 | 3.2 | 1.0-1.5 | 180/50 | 180 | 50 | 4.2 | 1.0-1.5 |
45/12 | 45 | 12 | 4.0 | 1.0-1.5 | 200/60 | 200 | 60 | 4.2 | 1.0-1.5 |
55/16 | 55 | 16 | 4.0 | 1.0-1.5 | 235/65 | 235 | 65 | 4.4 | 1.0-1.5 |
65/19 | 65 | 19 | 4.0 | 1.0-1.5 | 265/75 | 265 | 75 | 4.8 | 1.0-1.5 |
75/22 | 75 | 22 | 4.0 | 1.0-1.5 | 300/85 | 300 | 85 | 4.8 | 1.0-1.2 |
85/25 | 85 | 25 | 4.2 | 1.0-1.5 |
D* = Inner diameter as supplied
d* = Inner diameter after fully recovered