Description
Key Features:
Sealing Mastic Coating:
Provides superior sealing to prevent moisture and contaminants, enhancing the reliability and durability of cable connections.
Anti-Tracking Performance:
Prevents electrical tracking, ensuring the safety and longevity of the insulation, even in high-stress environments.
UV Resistant:
Built to withstand outdoor exposure without deterioration, ensuring performance in all weather conditions.
Flexible Shrink Ratio (2:3:1):
Adapts to various cable configurations and sizes, offering easy installation and versatile compatibility.
High-Temperature Recovery:
Fully recovers at a minimum temperature of 130℃, ensuring a tight and secure fit for optimal protection.
Applications:
Medium-Voltage Cable Terminations and Connections:
Ideal for installations requiring reliable insulation and protection against environmental factors such as moisture, UV light, and mechanical stress.
Rain Sheds, 3-Core Breakouts, Right-Angle Boots, and Straight Boots:
Perfect for cable breakout configurations, right-angle boots, and straight boots, ensuring robust protection for cable joints and terminations.
Shelf Life & Storage:
The RCS-AS / RCS-MB / RCS-MR heat shrink products have a shelf life of over 5 years from the manufacture date when stored in a humidity-controlled environment (Temperature range: -10°C to 40°C and <75% relative humidity).
Ordering Information:
Standard Color: Red
Why Choose RCS-AS / RCS-MB / RCS-MR Heat Shrink Molded Parts?
These anti-tracking heat shrink molded parts are ideal for medium-voltage cable applications, where superior insulation, protection, and environmental resistance are essential. Designed with a sealing mastic coating and anti-tracking properties, they provide a long-lasting, reliable solution for outdoor and industrial cable connections.
Typical technical performances:
Test Items | Test Method | Test Requirements |
Tensile strength | ASTM D 2671 | 12MPa min. |
Ultimate elongation | ASTM D 2671 | 200% min. |
Volume resistivity | IEC 93 | 1014Ω.cm min. |
Dielectric strength | IEC 60243 | 10kV/mm(3mm) min. |
Water absorption | ISO 62 | 0.5% max. |
Heat shock at 225℃/4hrs | ASTM D 2671 | No cracking, dropping |
Density | ASTM D 792 | 1.1~1.3g/cm3 |
Dimensions:
Anti-tracking rain shed-RCS-AS
Size | D2(mm) | As supplied(mm) | After recovered(mm) | |||
(mm) | a*(Min.) | b*(Min.) | H(Min.) | D1
(Nom.) |
W (±10%) | h(Min.) |
RCS-AS 110 35/12 | 35 | 12 | 20 | 95 | 3.0 | 18 |
RCS-AS 120 48/20 | 48 | 20 | 28 | 120 | 3.5 | 20 |
RCS-AS 130 60/25 | 60 | 25 | 30 | 120 | 3.3 | 20 |
RCS-AS 140 60/30 | 60 | 30 | 35 | 140 | 3.5 | 30 |
RCS-AS 150 75/30 | 75 | 30 | 35 | 140 | 3.3 | 30 |
RCS-AS 160 100/35 | 100 | 35 | 35 | 140 | 3.3 | 30 |
Anti-tracking 3 cores breakout-RCS-MB
Size |
As supplied (mm) ±10% |
D(mm)
|
I (mm)
|
Recovered length(mm)±10% | Recovered wall(mm)±20% | |||||
(mm) | l | f | a*(Min.) | b*(Max.) | a*(Min.) | b*(Max.) | L | F | Dw | Iw |
RCS-MB 320-60/ 25 | 175 | 38 | 60 | 25 | 26 | 8 | 170 | 40 | 3.0 | 2.5 |
RCS-MB 330-80/38 | 200 | 50 | 80 | 38 | 34 | 16 | 210 | 55 | 3.5 | 3.3 |
RCS-MB 340-110/50 | 210 | 55 | 110 | 50 | 46 | 19 | 230 | 55 | 3.8 | 3.5 |
RCS-MB 350-125/57 | 220 | 58 | 125 | 57 | 55 | 20 | 240 | 60 | 3.7 | 3.3 |
RCS-MB 360-140/70 | 250 | 58 | 140 | 70 | 62 | 26 | 270 | 65 | 3.8 | 3.6 |
Anti-tracking right/straight boot-RCS-MR
Size(mm) | As supplied
(mm) |
After recovered(mm) | ||||||||
D1
(Min.) |
D2
(Min.) |
D1
(Max.) |
D2
(Max.) |
L1
(Nom.) |
L2
(±10%) |
L
(±10%) |
W1
(±10%) |
W2
(±10%) |
||
Right Angle | RCS-MR 110(80/36-35/18) | 80 | 35 | 36 | 18 | 160 | 120 | / | 3.5 | 3.5 |
RCS-MR 120(80/36-50/18) | 80 | 50 | 36 | 18 | 160 | 120 | / | 3.5 | 3.5 | |
RCS-MR 130(80/36-50/27) | 80 | 50 | 36 | 27 | 145 | 135 | / | 3.6 | 3.3 | |
RCS-MR 140(95/38-70/28) | 95 | 70 | 38 | 28 | 155 | 130 | / | 4.2 | 4.5 | |
RCS-MR 150(145/72-68/34) | 145 | 68 | 72 | 34 | 195 | 145 | / | 3.8 | 3.8 | |
Straight | RCS-MR 170(80/35-58/20) | 80 | 58 | 35 | 20 | 145 | 30 | 200 | 3.0 | 3.0 |
RCS-MR 180(140/65-90/33) | 140 | 90 | 65 | 33 | 155 | 40 | 320 | 3.8 | 3.8 |
a* = As supplied
b* = After fully recovered